The Alpha E-Tec 28 is a 28.3 kW combi boiler, introduced in 2018, offering 93% seasonal efficiency and an ErP A-rating for heating and hot water.
The Alpha E-Tec 28 is a wall-hung condensing combi boiler designed for domestic heating and hot water provision in UK properties. Introduced in 2018, this model offers a maximum domestic hot water output of 28.3 kW and a central heating output of 24.1 kW. It is available in both natural gas and LPG variants, identified by their respective GC numbers 47 532 69 and 47 532 73. This appliance is suitable for engineers requiring detailed specifications, fault diagnostics, and service information.
Stick a QR tag on the case, scan it on every service and give your customer a permanent, shareable service history they can pull up from any phone.
Permanent, shareable service history
One QR scan on the boiler surfaces every previous fault, part change and visit — no paperwork to dig out.
Free AI fault diagnostics, built in
Every tag you fit unlocks the AI diagnostic tool for that exact model — paste a fault code, get a ranked cause list.
Your name on the boiler forever
When the next service or breakdown comes around the homeowner scans and sees your number first.
First 12 BoilerTags are free
Tag every install and service you do from now on — the subscription only kicks in once you scale past your first dozen.
Diagnosing a fault on a Alpha E-Tec 28 (NG) right now?
Try the free AI fault diagnostics tool — no signup needed.
Full technical specifications extracted from the manufacturer brochure. Empty sections are hidden.
Bottom connections for flow, return, gas, DHW inlet/outlet, condensate discharge
It is essential that the central heating system is thoroughly cleaned and flushed before fitting an Alpha E-Tec boiler. Failure to do so will invalidate the warranty. A proprietary cleaner should be used following the product manufacturers' instructions. After installation the system should then be filled and flushed before final filling. A corrosion inhibitor approved by Alpha must be added to ensure that the heating system operates effectively and efficiently, it is important to maintain the correct level of corrosion inhibition at all times. The corrosion inhibitor should be checked annually at the time of the boiler service, and topped up if necessary. A further dose of corrosion inhibitor should be added to the system every five years.
The Alpha E-Tec 28 combi boiler provides a maximum central heating output of 24.1 kW and a domestic hot water output of 28.3 kW, delivering a flow rate of 14.1 litres per minute at a 30°C temperature rise. It operates with a seasonal efficiency of 93% and holds an ErP A-rating for both heating and domestic hot water, with an XL hot water profile. The appliance features a stainless steel primary heat exchanger and a modulating pump with 9 speed settings, offering an available head of 7 metres.
Installation requires specific clearances, including 450mm front and 235mm top, and mandates thorough system cleaning and the use of corrosion inhibitor to maintain warranty validity. The E-Tec 28 supports OpenTherm compatible controls and includes integrated frost protection and a built-in timer. Its compact dimensions of 712mm height, 440mm width, and 268mm depth, combined with a dry weight of 33.6 kg, facilitate wall-hung installation in various domestic settings.
Every fault code listed in the manufacturer brochure, with likely causes and engineer actions. Each code has a permalink — paste a URL like https://www.boilertag.com/boilers/alpha/e-tec-28-ng#fault-01 to jump straight to the entry.
| Code | Meaning | Details |
|---|---|---|
| 01 | Ignition failure Show causes & actionsFlame not detected during ignition sequence Likely causes
| Details |
| 02Lockout | Overheat boiler lock out Show causes & actionsOverheat sensor has activated Likely causes
| Details |
| 03 | High flue temperature Show causes & actionsFlue sensor intervention (flue temperature too high) Likely causes
| Details |
| 04 | Gas valve electrical connection fault Show causes & actionsGas valve wiring circuit fault detected Likely causes
| Details |
| 05 | CH flow sensor fault Show causes & actionsIncorrect flow sensor resistance value Likely causes
| Details |
| 06 | DHW sensor fault Show causes & actionsDHW sensor resistance value is incorrect Likely causes
| Details |
| 08Lockout | Max. number of resets Show causes & actionsMaximum number of resets reached (5) Likely causes
User action Refer to fault history codes (INFO menu d9), to reset by turning the boiler off and on. Engineer action If it will not clear replace PCB Reset procedure turning the boiler off and on | Details |
| 10 | Primary system pressure low Show causes & actionsPrimary pressure switch has operated Likely causes
| Details |
| 12 | DHW inlet sensor fault Show causes & actionsOptional DHW inlet sensor resistance out of range Likely causes
| Details |
| 15 | Incorrect configuration Show causes & actionsIncorrect hydraulic configuration There is an inconsistency between the settings and signals received from the PCB Likely causes
| Details |
| 16 | Fan fault Show causes & actionsFan wiring fault or fan faulty Likely causes
| Details |
| 20 | Flame sensing fault Show causes & actionsFalse flame detection Flame detected but gas valve is not open Likely causes
| Details |
| 22 | PCB fault Show causes & actionsPCB software error Likely causes
Engineer action Replace PCB | Details |
| 23 | Return sensor fault Show causes & actionsReturn sensor resistance out of range Likely causes
| Details |
| 24 | Control panel button fault Show causes & actionsControl panel button stuck in the on position Likely causes
| Details |
| 25 | PCB fault Show causes & actionsPCB fault - software error Likely causes
Engineer action Replace PCB | Details |
| 27 | Primary circuit overheat Show causes & actionsInsufficient circulation in primary circuit causing overheating Likely causes
| Details |
| 29 | Flue sensor fault Show causes & actionsFlue sensor resistance out of range Likely causes
| Details |
| 31 | Loss of communication with external control (Alpha Climatic) Show causes & actionsLoss of connection between the boiler and Alpha Climatic control unit Likely causes
| Details |
| 37 | Low supply voltage Show causes & actionsInsufficient supply voltage to operate boiler Likely causes
| Details |
| 38 | Loss of flame rectification Show causes & actionsFlame detected but signal lost. Ignition retries after fan purge Likely causes
| Details |
| 43 | Loss of flame rectification Show causes & actionsRepeated loss of flame signal during operation This fault can occur if the flue is exposed to high wind conditions (shown as E38 in the fault code history in the INFO menu) Likely causes
| Details |
| 45 | High ΔT Show causes & actionsThe boiler detects a sudden, unexpected increase in ΔT between the flow sensor and the system return sensor Likely causes
| Details |
| 47 | Reduced burner output Show causes & actionsFlue thermostat has sensed high flue gas temperature (110°C) and reduced the burner output to prevent damage. If the temperature continues to rise the boiler will lock out and E03 will be displayed Likely causes
| Details |
| 51 | Climatic RF communication fault Show causes & actionsError between communication of the Climatic transmitter and boiler receiver Likely causes
| Details |
| 60 | Pump fault Show causes & actionsThe pump is stuck or there is an electrical pump fault Likely causes
| Details |
| 61 | Air in the pump Show causes & actionsRestricted CH flow due to air or a circuit restriction Likely causes
| Details |
| 70 | Return/flow sensor error (return reading higher than flow) Show causes & actionsPossible wiring fault, sensors incorrectly fitted, system blocked Likely causes
| Details |
| 75 | Return/flow sensor fault Show causes & actionsPossible failure of one or both sensors Likely causes
| Details |
| 76 | Return/flow sensor fault Show causes & actionsPossible failure of one or both sensors Likely causes
| Details |
| Sr | Service reminder Show causes & actionsService reminder count down (0 - 36 months) has reached zero. See Section 6.13, parameter P6. Note: E97 is also shown on Climatic controller, if used User action Note: The 'Sr' code will not stop the boiler functioning Note: Pressing the RESET button will clear the 'Sr' code for 24 hrs to allow the display to be read Engineer action To permanently reset the error 'Sr' / E97 1. Enter the parameter menu using the password 69. See Section 6.13 2. Parameter P6 will show 0 3. Set P6 to any value above zero, save by pressing the mode button (1) and wait for '88' to be displayed as confirmation 4. Then set P6 to 0, save by pressing the mode button (1) and wait for '88' to be displayed as confirmation 5. Now set the parameter P6 at the number of months to the next service reminder (i.e. 12 for one year). Save by pressing the mode button (1) and wait for '88' to be displayed as confirmation | Details |
| Boiler completely turned off | Boiler completely turned off Show causes & actionsScreen only shows a single dot to indicate boiler is completely off User action Press mode button (1) for 2 seconds then release. Boiler display will return and you can select an operating mode | Details |
| Boiler fused blown | Boiler fused blown Show causes & actionsFuse on main PCB blown Likely causes
| Details |
Patterns that group across the manufacturer's fault-code table. Each entry links to the full code listing further down the page.
Triggered by fault code 02.
User: Refer to fault history codes (INFO menu d9), to reset by turning the boiler off and on.
Engineer: If it will not clear replace PCB
Triggered by fault code 08.
Triggered by fault code 01.
Triggered by fault code 03.
Triggered by fault code 04.
Common questions from engineers and homeowners about the Alpha E-Tec 28 (NG).
Parts referenced in the manufacturer brochure for routine service and repair.
3.0252301.0346001.0392441.0235811.0394761.0394771.0396731.0302513.0277021.0353651.0381623.0276973.0276981.0406691.0406701.0259101.0339181.0272773.0227833.0216931.0370311.0285611.0399441.0271101.0378901.0392083.0276993.0267943.0277713.0253233.0277721.0391401.0378161.0267631.0203932.0153503.0248933.0268801.0397761.0391411.0242961.040351We hold the Alpha E-Tec 28 (NG) manual — and every other UK boiler and heat pump brochure. Sign up and pull any model up from your phone, on the job.
Sign up to access brochuresTag it before you leave. Next scan shows every service, fault and part change — and the AI diagnostic tool is free on every tag you fit.
Specifications on this page are extracted from the manufacturer brochure. Always cross-check against the latest datasheet before commissioning or quoting. Last updated 28 June 2026.