Free calculator for engineers
Radiator BTU Calculator
The right output, every room. Dimensions, insulation, glazing — we give you BTU, watts, and a short list of suitable radiators from Type 11 through Type 33.
Required output
(1,440 W · 28.8 m³ volume)
Suitable radiators
Type 22 double 600 × 1000
1,830 W · 6,244 BTU(+27%)
Type 22 double 600 × 1400
2,565 W · 8,752 BTU(+78%)
Type 22 double 600 × 1800
3,295 W · 11,243 BTU(+129%)
Outputs based on Δt 50 °C. Derate by ~17% for Δt 40 °C (heat pump flow) or ~30% for Δt 30 °C.
How it works
- 1
Measure the room
Length, width and ceiling height in metres. Tape-measure accuracy is fine.
- 2
Describe the fabric
Room type, insulation level, number of external walls, glazing and whether neighbouring rooms are heated.
- 3
Read the required output
The tool gives you BTU and watts instantly, plus suitable Type-11, 21, 22 and 33 radiator sizes.
How we calculate the output
The starting point is the room volume (length × width × height) multiplied by a room-type factor in watts per cubic metre. Living rooms, dining rooms and bathrooms need more heat per m³ than bedrooms, kitchens or hallways because of comfort set-points and dwell time.
From there we apply four correction factors:
- Insulation. Poor insulation pushes the output up by 25%; good insulation brings it down by 15%.
- External walls. A fully internal room gets a small discount; a three-external-wall corner room gets a 20% penalty.
- Glazing. Single glazing adds 15%. North-facing adds a further 10%.
- Heated neighbours. Heated rooms above and/or below each knock 5% off the load.
The result is a Δt 50 design load. If the room is served by a heat pump flowing at lower temperatures, derate the radiator output by 17% for Δt 40 or 30% for Δt 30. In other words: a radiator rated 1,830 W at Δt 50 gives roughly 1,520 W at Δt 40 and 1,280 W at Δt 30.
Common sizing mistakes
Sizing for the boiler, not the room. A radiator needs to replace the room's heat loss. Boiler kW is a totally separate calculation — see our boiler size calculator.
Using towel rail output for the whole bathroom. Towel rails often provide less than half the required output on their own. Add a compact radiator below the window where possible.
Oversizing "just in case". Radiators much larger than the load cycle on and off aggressively, especially on modulating combi boilers — the room overheats, the flow temperature doesn't stabilise, and condensing mode is lost. Size for the load, not for peace of mind.
Tag it once. Get rebooked every year.
Stick a BoilerTag on the boiler. The homeowner scans the QR when the service is due — your name and number are right there. Your first 12 tags are free.
Get 12 free BoilerTagsFrequently asked questions
Heat loss calculator →
Whole-house heat loss for heat pump and boiler sizing conversations.
Boiler size calculator →
Work out the right kW output for a replacement combi or system boiler.