Ideal Logic: 2016 Propane Logic + Heat that won’t ignite,

Published 22 July 2026 · Generated by BoilerTag's diagnostic AI from an engineer's real-world submission

One of 15 real-world fault checklists on BoilerTag, across 6 boiler makes.

Most likely cause

The Ideal Logic + Heat boiler failing to ignite, despite new spark generator and electrode, 37mbar standing pressure dropping to 34mbar on ignition attempt, and 233V DC to the gas valve, points towards a persistent ignition lockout. Common causes for ignition lockout (often indicated by an L2 fault code on Ideal Logic boilers) include issues with gas supply, gas valve, flue/air intake, condensate, flame rectification, or the PCB. Given the steps already taken, further investigation into gas valve resistance, flame rectification, and potential PCB faults is crucial.

The engineer's report

A gas engineer submitted this case through BoilerTag's free fault diagnostic tool, working on a Ideal Logic. They described the behaviour they were seeing on site as follows:

2016 Propane Logic + Heat that won’t ignite, Spark generator and electrode are brand new from another engineer. Got 37mb standing pressure dropping to 34 when it tries to light. Got 233v DC to the gas valve. Lead is sound. Spark generator lead is also sound. At a bit of a loss on this one tbh. Any other tests I can look at? Cheers in advance!

BoilerTag's diagnostic AI then cross-checked manufacturer documentation and common trade knowledge to produce the prioritised checklist below.

Diagnostic checklist

Email me this checklist

Get the full Ideal Logic diagnostic — steps, safety notes and parts — sent to your inbox to keep or share on site.

More Ideal fault codes

Browse all Ideal fault diagnostics →

Sources

The AI cross-checked the following manufacturer and trade sources while producing this checklist.

Tag it once. Get rebooked every year.

Stick a BoilerTag on the boiler. The homeowner scans the QR when the service is due — your name and number are right there. Your first 12 tags are free.

Get 12 free BoilerTags

This checklist is provided for reference only. Always follow manufacturer documentation and stay within Gas Safe scope. BoilerTag does not replace a qualified engineer's own judgement.

Fixed a fault the hard way? Add your fix — help the next engineer →